VEGASON 51P 53P 49
Setup
Choose " .
In the menu window "Min/Max-Adjustment
you choose e.g. the level distance corre-
sponding to 100 % and 0 %. Of course, you
can also enter the distance values e.g. at
20 % and 75 % filling.
If the two points are too close together, e.g. at
45 % and 49 %, this can cause a consider-
able meas. error, as the sensor generates by
means of the two adjustment points a linear
correlation between filling volume (%) and
meas. distance.
Choose if you want to carry out the adjust-
ment in
meters
(m) or in
feet
(ft).
Enter a distance for the upper and lower
level and the extent of filling in % corre-
sponding to each distance.
In the example, the 0 % filling is at a product
distance of 5.850 m and the 100 % filling at a
product distance of 1.270 m.
Confirm the adjustments with " and
after a message is displayed, you are
again in the menu window "
Adjustment
.
Note:
The sensor is delivered with the measuring
range set to the same value as the operating
range. After the sensor has been adjusted,
the operating range corresponds to the ad-
justment range. The sensor can only detect
levels within the defined operating range. For
level detection outside the operating range,
e.g. if you want to detect 108 % and -10 %,
the operating range must be corrected ac-
cordingly in the menu "
Sensor optimisation/
Meas. environment
(see the following chap-
ter "Sensor optimisation, "Meas. environ-
ment/Operating range).
Click in the menu window "
Adjustment
to
" .
You are again in the menu window "
Instru-
ment data parameter adjustment
.